Not sure which UPS fits your load? Our engineers will help you choose

Calculating the Capacity and Number of Batteries Needed for a UPS Unit

Battery

First: Calculating the battery capacity

To calculate the battery capacity required to power a UPS system, use the following formula:

Battery capacity calculation formula

  • KVA : Power required by Loads
  • p.f : Power Factor of Load
  • Inverter Efficiency (DC to AC Conversion Efficiency) : Given by manufacturer
  • Number of cells (Given by manufacturer)

Example: Suppose the total power of the loads (the UPS rating) is 300 kVA, the power factor of these loads is 0.8, and the inverter efficiency is 94%. The UPS is to power these loads for 30 minutes (back up time).

Calculate the number of batteries required to power the loads.

Answer

First: calculating the number of cells (Number of cells) using the formula above

Suppose the UPS voltage, which equals the DC Bus Voltage, is 480 volts,

and the required battery voltage is 12 volts, where each battery consists of 6 cells and each cell has a voltage of 2 volts,

so (battery voltage = number of cells × voltage of one cell = 6 × 2 = 12 volts).

The number of batteries required in one bank = total voltage / battery voltage = 480 / 12 = 40 batteries.

batteries / bank = 40 battery

The number of cells required for one bank = number of batteries in the bank × 6 = 40 × 6 = 240 cells.

Cells / bank = 240 cell

Calculating UPS runtime

Calculating the back up time of the UPS batteries.

To calculate the back up time from the battery capacity, we use the following formula:

Back up time calculation formula

Still need help?

Ask the MYE assistant or contact the team.

Call now